| A Relay
General Application Guidelines
A relay
may encounter a variety of ambient conditions during actual use
resulting in unexpected failure. Therefore, testing over a practical
range under actual operating .conditions
is necessary. Application considerations should be reviewed and
determined for proper use of the relay.
METHOD OF DETERMINING SPECIFICATIONS
In order to use
the relays properly, the characteristics of the selected relay should be well
known, and the conditions of use of the relay should be investigated to
determine whether they are matched to the environmental conditions,contact
conditions, and the ambient conditions for the relay that is actually used must
be sufficiently in advance. In the table below, s summary had been made of the
points of consideration for relay selection. It may be used as a reference for
investigation of items and points of caution.
|
Specification item |
consideration points regarding selection |
| Coil |
a)Rating
b)Pick-up voltage (current)
c)Drop-out voltage (current)
d)Maximum conditions impressed voltage (current)
e)Coil resistance
f)Impedance
g)Temperature rise
h)Input frequency for AC type |
1)Select relay with consideration for power source ripple.
2)Give sufficient consideration to ambient temperature and the coil temperature rise.
3)When used in conjunction with semiconductors, addition attenton to the application should be taken.
|
|
Contacts |
a)Contact arrangement
b)Contact rating
c)Contact material
d)Life
e)Contact pressure
f)Contact resistance |
1)It is desirable to use a standard product with more than the required number of contacts.
2)It is beneficial to have the relay life balanced with the life of the device it is used in.
3)Is the contact material matched to the type of load?
It is necessary to take care particularly with low level usage.
|
|
Operate time |
a)Operate
b)Release time
c)Bounce time
d)Switching frequency |
1)It is beneficial to have the bounce time short for sound circuits and similar applications.
|
|
Mechanical characteristics |
a)Vibration resistance
b)Shock resistance
c)Ambient temperature
d)Life |
1)Give consideration to performance under vibration and shock in the use location.
2)In particular, when used in high temperature application, relay with class B or class F coil insulation may be required.
|
|
Other item |
a)Mounting method
b)Cover
c)Size |
1)Selection can be made foe connection method with plug-in type, printed circuit board type, soldering, tab terminal, and screw fastening type.
2)For use in an adverse atmosphere, sealed construction type should be selected.
3)Are there any special condition?.
|
BASICS ON RELAY HANDLING
.To
maintain initial performance, care should be taken to avoid dropping or hitting
the relay.
.Under
normal use, the relay is designed so that the relay will not detach. To
maintain initial performance, the care should not be removed. Relay
characteristics cannot be guaranteed if the case is removed.
.Use
of the relay in an atmosphere at standard temperature and humidity with
minimal amount of dust, SO2, H2S, or organic gases
is recommended. Also note that use of silicon-based resins near the
relay may result in contact failure. For installation in advance
environment, one of the sealed types (plastic sealed type, etc.) should
be considered.
.Care
should be taken to observe correct coil polarity (+, -) for polarized
relays.
.Proper
usage required that the rated voltage be impressed on the coil. Use
rectangular waves for DC coils and sine waves for AC coils.
.Be
sure the coil impressed voltage does not continuously exceed the maximum
allowable voltage.
.Absolutely
avoid using switching voltages and currents that exceed the designated
values.
.The
rated switching power and life are given only as guides. The physical
phenomena at the contacts and contact life greatly very depending on the
type of load and the operating conditions. Therefore, be sure to
carefully check the type of load and operating conditions before use.
.Do
not exceed the usable ambient temperature values listed in catalog.
.Use
the flux-resistance type or sealed type if automatic soldering is to be
used.
.Use
Freon or alcohol based cleaning solvents when cleaning is to be
performed using a sealed type relay.
.Avoid
ultrasonic cleaning of all types of relays.
.As
a guide, use a Faston mounting pressure of 4 to 7kg or 8.8 to 15.4lbs
for relays with tab terminals.
.For
proper use, read the main text for details.
PROBLEM POINTS WITH REGARD TO USE
In the actual use of relays, various ambient conditions are encountered, and because unforeseen events occur which can not be though of on the drawing board, witch regard to the conditions, tests are necessary under the possible range of operation. For example, consideration must begiven to variation of performance when relay characteristics are being reviewed. The relay is a mass production item, and as a matter of principle, it must be recognized that the relay is to be used to the extent of such variations without the need for adjustment.
RELAY COIL
.AC operation type
For the
operation of AC relays, the power source is almost a commercial frequency (50 or
60HZ) with standard voltage of 6, 12, 24, 48, 110, 220 and 240V AC. Because of
this, when the voltage is other than the standard voltage, the product is
special order item, and the factor of price, delivery, and stability of
characteristics may create inconveniences. To the extent that it is possible,
the standard voltage should be selected.
Also, in
the AC type, shading coil resistance loss, magnetic circuit eddy current
loss, and hysteresis loss exit, and because of lower coil efficiency, it
is normal foe the temperature rise to be greater than that for the DC
type. furthermore, because humming occurs below the level of pick-up
voltage (minimum operation voltage), care is required with regard to
power source voltage fluctuation.
For
example, in the case of motor starting, if the power source voltage
drops, and during the humming of relay, if it reverts to restored
condition, the contact suffer a burn damage and welding, with the
occurrence of s false operation self-maintaining condition.
For the
AC type, there is a inrush current during the operation time (for the
separated condition of the armature, the impedance is low and a current
greater than rated current flows; for the adhered condition of armature,
the impedance is high and the rated value current flows), and because of
this, for the case of several relays being used in parallel condition,
it is necessary to give consideration to power consumption.
.DC
operation type
For the
operation of DC relays, standards exist for power source voltage and
current, with DC voltage standards set at 5, 6, 12, 24, 48 and 100V, but
with regard to current, the values as expressed in catalogues in
milliamperes of pick-up current.
However,
because the value of pick-up current is nothing more than a guarantee of
just barely moving the armature, the variation in impressed voltage and
resistance values, and the increase in coil resistance due to
temperature rise, must be given consideration for the worst possible
condition of relay operation, making it necessary to consider the
current value as 1.5 to 2 times the pick-up current. Also, because the
extensive use of relays as limit devices in place of meter for both
voltage and current, and because of the gradual increase or decrease of
current impressed on the coil causing possible delay in movement of the
contacts, there is the possibility that the designated control capacity
may not be satisfied. Thus it is necessary to exercise care. The DC type
relay coil resistance varies due to ambient temperature as well as to
its own heat generation to extent of about 0.4%/°C,
and accordingly, if the temperature increases in pick-up and drop-out
voltage, care is required.
.Impressed
voltage of AC coil
in order
to have stable operation of the relay, the impressed voltage should be
basically within the range of of the rate voltage. However, it is
necessary that the waveform of the voltage impressed on the coil be a
sine wave. There is no problem if the power source is commercially
provided power, but when a stabilized AC power source is used, there is
a waveform distortion due to that equipment, and there is the
possibility of abnormal overheating. By meanings of shading coil for the
AC coil, humming is stopping, but with a distorted waveform, that
function is not displayed. Fig. 1 below shows an example of waveform
distortion.

Fig.
1 Distortion in an AC stabilized power source
If the
power source of relay operating circuit is connected to the same line
the motors, solenoids, transformers, and other loads, when these load
operate, the line voltage drops, and because of this the relay contacts
suffer the effect of vibration and subsequent burn damage. In
particular, if a small type transformer is used and its capacity has no
margin of safety, when there is long wring is slender, it is necessary
to take precautions because of the normal voltage fluctuation combined
with these other factor. When trouble develops, a survey of the voltage
situation should made using a synchroscope or similar means, and the
necessary counter-measures should be taken, and together with this
determine whether the special relay with suitable excitation
characteristics should be used, or make a change in the DC circuit as
shown in Fig. 2 in which a capacitor is inserted to absorb the voltage
fluctuation.

Fig.
2 Voltage fluctuation absorbing circuit using a condenser
In
particular, when a magnetic switch is being used, because the load
becomes like that a motor, depending upon the application, separation of
the operating circuit and power circuit should be tried and
investigated.
.Power
source for DC input
As a
power source for the DC type relay, a battery or either a half wave or
full wave rectifier circuit with a smoothing capacitor is used. The
characteristics with regard to the excitation voltage of the relay will
change depending upon the type of power source, and because of this, in
order to display stable characteristics, the most desirable method is
perfect DC.
In the
case of ripple included in the DC power source, particularly in the case
of half wave rectifier circuit with a smoothing capacitor, if the
capacity of the capacitor is too small, due to the influence of the
ripple, humming develops and an unsatisfactory condition is produced.
With the actual circuit to be used, it is absolutely necessary to
confirm the characteristics.
.Coil
temperature rise
Proper
usage requires that the rated voltage be impressed on the coil. Note,
however, that if a voltage greater than or equal to the maximum
continuous impressed voltage is impressed on the coil, the coil may burn
or its layers short due to the temperature rise. Furthermore, do not
exceed the usable ambient temperature range listed in catalog.
.Temperature
rise due to pulse voltage
When a
pulse voltage with ON time of less than 2 minutes is used, the coil
temperature rise bares no relationship to the On time. This various with
the ratio of On time to OFF time, and compared with continuous current
passage, it is rather small. The various relays are essentially the same
in this respect. (Fig. 3).
|
Current passage time |
﹪ |
|
For continuous passage |
Temperature rise value is 100﹪ |
|
ON:OFF=3:1 |
About 80﹪ |
|
ON:OFF=1:1 |
About 50﹪ |
|
ON:OFF=1:3 |
About 35﹪ |

Fig.
3
.Pick-up
voltage change due to coil temperature rise (hot start) In
DC relays, after continuous passage of current coil, if the current is
turned OFF, then immediately turned ON again, due to the temperature
rise in the coil, the pick-up voltage will become somewhat higher. Also,
it will be the same as using it in a higher temperature atmosphere. The
resistance/temperature relationship for copper wire is about 0.4% for 1°C,
and with ratio the coil resistance increase. That is, in order to cause
operation of the relay, the current necessary becomes higher than the
pick-up current, accompanying the rise in the resistance value.
.Operate
time
In the
case of AC operation, there is extensive variation in operate time
depending upon the point in the phase at which the switch is turned ON
for coil excitation, and it is expressed as a certain range, but for
miniature types it is for the most part 1/2 cycle (about 10msec.).
However, for the somewhat large type relay where bounce is large, the
operate time is 7 to 16msec., with the release time in the order of 9 to
18msec. Also, in the case of DC operation, to the extent of large coil
input, the operating time is rapid, but if it is
too rapid, the “A” contact bounce time is extended.
.Stray
circuit (bypass circuits)
In the
case of sequence circuit construction, because of bypass flow or
alternate routing, it is necessary to take care not to have erroneous
operation or abnormal operation. To understand this condition while
preparing sequence circuits, as shown in Fig. 4 with two lines written
as the power source lines, the upper line is always (+) and lower line
(-) (when the circuit is AC, the same thinking applies). Accordingly the
(+) side is necessary the side for making contact connections (contacts
for relays, timers, limit switches, etc.), and the (-) side is the load
circuit side (relay coil, timer coil, magnet coil, solenoid coil, motor,
lamp, etc.).

Fig. 4 Example of a vertically written sequence circuit
Fig. 5
shows a example of stray circuit. In Fig. 5(a), with contacts A, B, and
C closed, after relays R1, R2, and R3
and the relays will hum and sometimes not be restored to the drop out
condition.
The connection shown in Fig. 5(b) are correctly made. In addition, with
regard to the DC circuit, because it is simple by means of a diode to
prevent stray circuits, proper application should be made.

Fig. 5 Stray circuits
.Gradual
increase of coil impressed voltage and suicide circuit
When the
voltage impressed on the coil is increased slowly, the relay transfering
operation is unstable, the contact pressure drops contact bounce
increases, and an unstable condition of contact occurs. This method of
applying voltage to the coil should not be used, and consideration
should be given to the method of impressing voltage on the coil (use of
switching circuit). Also, in the case of latching relays, using self
contacts “B”, the method of self coil circuit for complete interruption
is used, but because of the possibility of trouble developing, care
should be taken. The circuit shown in Fig. 6 causes a timing and
sequential operation using a reed type relay, but it is not a good
example with mixture of gradual increase of impressed voltage for the
coil and a sucide circuit. In the timing portion for relay R1,
when the timing times out, chattering occurs causing trouble. In the
initial test (trial production), it shows favorable operation, but as
the number of operations increases, contact blackening (carbonization)
plus the chattering of the relay creates instability in performance.

Fig.
6 A timing and sequential operation using a reed type relay
.Phase
synchronization in AC load switching
If
switching of the relay contacts is synchronized with the phase of the AC
power, reduced electrical life, welded contacts, or a locking phenomenon
(incomplete release) due to contact material transfer may occur.
Therefore check the relay while it is operating in the actual system.
However, if problem develop, control the relay using an appropriate
phase. (Fig. 7).

Fig. 7
.Erroneous
operation due to inductive interference
In
situations where both control and load wiring are in close proximity,
thought should be given to separating or shielding the conductors in
order to prevent false relay operation. This becomes increasingly
important with long wire runs, and can be achieved by using separate
conduit for load control conductor. Inductive coupling can also be
minimized of the load and control wiring.
.Influence
of external magnetic fields
Many
modern electro-mechanical relays are of polarized, high sensitivity
design. Care should be exercised in the placement of these devices when
strong, external magnetic fields are prevent, such as in proximity to
power transformers or permanent magnets (speaker, etc.).
Operational characteriatics may change under an external magnetic
influence.
.Long
tern current carrying
In
application \s which involve lengthy duty cycles, the preferred
configuration would be the use of the form B or N.C. contacts for long
term duty. In those instances where the form A contact is held closed
for extensive time period, coil heating will increase contact “T” rise
and may result in shorter than optimum life. Alternately, latching types
may be considered for these applications, using a storage capacitor to
“Reset” the relay on power-down.
.Regarding
electrolytic corrosion of coils
In the
case of comparatively high voltage coil circuit (in particular above 48V
DC), when such relays are used in high temperature and high humidity
atmospheres or with continuous passage of current, the corrosion can be
said to be the result of the occurrence of electrolytic corrosion.
Because of the possibility of open circuit occurring, attention should
be given to the following points.
The (+)
side of the power source should be connected to the chassis. (Refer to
Fig. 9) (Common to all relays)
In the
case where unavoidably the (-) side is grounded, or in the case where
grounding is not possible.
Insert
the contacts (or switch) in the (+) side of the power source, and
connect the start of the coil winding the (-) side. (Refer to Fig. 10)
(Common to all relay)
When a
grounding is not required, connect the ground terminal to the (+) side
of the coil. (Refer to Fig. 11) (NF and NR with ground terminal).
.Contact
Protection Circuit
Use of
contact protective devices or protection circuits can suppress the
counter emf to a low level. However, note thatincorrect use will result
in an advance effect. Typical contact protection circuits are given in
the table blow.
|
Circuit |
Application |
Features/Others |
Device Selection |
| AC |
DC |
|
CR circuit |
 |
* |
○ |
If the load is a timer, leakage current flows through the CR
circuit causing faulty operation.
*If used with AC voltage, be sure the impedance of the load is
sufficiently smaller than that of the CR circuit. |
As a guide in selecting r and c,
r:0.5 to 1W
per 1V contact voltage
c:0.5 to 1mF per
1A contact current
Values vary depending on the properties of the load and the
variations in relay characteristics.
Capacitor c acts to suppress the discharge the moment of
contacts open. Resistor r acts to limit the current when the
power is turned on the next time. Test to confirm. Use a
capacitor with a breakdown voltage of 200 to 300V. use AC type
capacitors (non-polarized) for AC circuits |
|
 |
○ |
○ |
If the load is a relay or solenoid, the release time lengthens.
Effective when connected to both contacts if the power supply
voltage is 24 or 48V and the voltage across the load is 100 to
200V. |
|
Diode circuit |
 |
× |
○ |
The diode connected in parallel causes the energy stored in the
coil to flow to the coil in the form of current and dissipates
it as joule heat at the resistance component of the inductive
load. This circuit further delays the release time compared to
the CR circuit. (2 to 5 times the release time listed in the
catalog). |
Use a diode with a reverse breakdown voltage at least 10 times
the circuit voltage and a forward current at least as large as
the load current. In electronic circuit where the circuit
voltage are not so high, a diode can be used with a reverse
breakdown voltage of about 2 to 3 times the power supply
voltage. |
|
Diode and zener diode circuit |
 |
× |
○ |
Effective when the release time in the diode circuit is too
long. |
Use a zener diode with a zener voltage about the same as the
power supply voltage. |
|
Varistor circuit |
 |
× |
○ |
Using the stable voltage characteristics of the varistor, this
circuit prevent excessively high voltage from being applied
across the contacts. This circuit also slightly delays the
release time. Effective when connected to both contacts if the
power supply voltage is 24 or 48V and the voltage across the
load is 100 to 200V. |
|
.Avoid
using the protection circuits shown in the Fig. 8. Although DC inductive
loads are usually more difficult to switch than resistive loads, use of
the proper protection circuit will raise the characteristics to that for
resistive loads.
 Fig. 8 |
Although extremely effective in arc suppression as the contacts
open, the contacts are susceptible to welding since energy is
stored in C when the contacts open and discharge current flows
from C when the contacts close. |
 |
Although extremely effective in arc suppression as the contacts
open, the contacts are susceptible to welding since charging
current flows from C when the contacts close. |
.Mounting
the Protective Device
In the
actual circuit, it is necessary to locate the protective device (diode,
resistor, capacitor, varistor, etc.) in the immediate vicinity of the
load or contact. If located too far away, the effectiveness of the
protective device may diminish. As a guide, the distance should be
within 50cm.
.Abnormal
Corrosion During High Frequency Switching of DC loads (spark generation)
If, for
example, a DC value or clutch is switched at s high frequency, a
blue-green corrosion may develop. This occurs from the reaction with
nitrogen in the air when sparks (arc discharge) are generated during
switching. For relays with a case, the case must be removed or air holes
drilled in the case. A similar phenomenon occurs in the presence of
ammonia-based gas. Therefore, care is required in circuits where sparks
are generated at a high frequency.
.Type
of load and Inrush Current
The type
of load and its inrush current characteristics, together with the
switching frequency are important factors which cause contact welding.
Particularly for load with inrush currents, measure the steady state
current and inrush current and select a relay which provides an ample
margin of safety. The table on the right shows the relationship between
typical loads and their inrush currents.
|
Type of load |
Inrush current |
|
Resistive load |
Steady state current |
|
Solenoid load |
10 to 20 times the steady state current |
|
Motor load |
5 to 10 times the steady state current |
|
Incandescent lamp load |
10 to 15 times the steady state current |
|
Mercury lamp load |
Approx. 3 times the steady state current |
|
Sodium vapor lamp load |
1 to 3 times the steady state current |
|
Capacitive load |
20 to 40 times the steady statecurrent |
|
Transformer load |
5 to 15 times the steady state current |
Load
Inrush Current Wave and Time
 
. When
Using Load Wires
If long
wires (100 to 300m) are to be used in a relay contact circuit, inrush
current maybe become a problem due to the stray capacitance exiting
between wires. Add a resistor (approx. 10 to 50W)
in series with the contacts. (fig. 9)

Fig.9
.Phase
Synchronization in Switching AC Loads
If
switching of the relay contacts is synchronized with the phase of the AC
power, reduced electronic life, welded contacts, or a locking phenomenon
(incomplete release) due to contact material transfer may occur.
Therefore, check the relay while it is operating in the actual system.
However, if problem develop, control the relay using an appropriate
phase. (Fig. 10).

Fig.10
.Connection
of load and contacts
Connect
the load to the side of power supply as shown in Fig. 11(a). connect the
contacts to the other side. This prevents high voltage from developing
between contacts. If contacts connected to both side of the power supply
as shown in (b), there is a risk of shorting the power supply when
relatively close contacts short.

Fig.11
RELAY
DRIVE BY MEANS OF A TRANSISTOR
.Connection
method
The
voltage impressed on the relay is always full rated voltage, and in the
OFF time, the voltage is complete zero for avoidance of trouble in use.
(Fig. 1)

Fig.1
.Countermeasures
for surge voltage of relay control transistor
If the
coil current is suddenly interrupted, a sudden high voltage pulse is
developed in the coil. If this voltage exceeds the voltage resistance of
the transistor, the transistor will be degraded, and this will lead to
damage. It is absolutely necessary to connect a diode in the circuit as
a means of preventing damage from the counter emf.
As
suitable ratings for this diode, the current should be equivalent to the
average rectified current to the coil, and the inverse blocking voltage
should be about 3 times the value of the power source voltage. (Fig. 2)

Fig.2
.Snap
action
(Characteristic of relays with voltage rise and fall of voltage)
Unlike
the characteristic when voltage is impressed slowly on the relay coil,
this is the case where it is necessary to impress the rated voltage in a
short time and also to drop the voltage in a short time. (Fig. 3)

Fig. 3
.Schmitt
circuit (Snap action circuit)
(Wave
rectifying circuit)
When the
input signal does not product a snap action, ordinarily a Schmitt
trigger circuit is used to product safe snap action.
Characteristic points
1. The
common emitter resistor RE must have a value sufficiently
small compared with the resistance of the relay coil. (The voltage
impressed on the relay must not be greater than the excitation voltsge.)

Fig. 4
2. Due
to the relay coil current, the difference in the voltage at point P when
T2 is conducting and at point P when T1 is
conducting creates hysteresis in the detection capability of the Schmitt
circuit, and care must be taken in setting the values.
3. When
there is chattering in the input signal because of waveform oscillation,
an RC time constant circuit should be inserted in the stage before the
Schmitt trigger circuit. (However, the response speed drops.) (Fig. 4)
.Avoid
Darlington circuit connection
(High
amplification)
This
circuit is a trap into which it is easy to fall when dealing with high
circuit technology. This does not mean that it is immediately connected
to the defect, but it is linked to troubles that occur after long
periods of use and with many units in operation. (Fig.5)

Fig. 5
.Residual
Coil Voltage
In
switching applications where a semiconductor (transistor, UJT, etc.) is
connected to the coil, a residual voltage is retained at the relay coil
which mat cause incomplete restoration and faulty operation. By using DC
coil, there may be a reduction in; the danger of the incomplete
restoration, the contact pressure, and the vibration resistance. This is
because the drop-out voltage is 10% or more of the rated voltage, a low
value compared to that for AC coil, and also there is a tendency to
increase the life by lowering the drop-out voltage. When the signal from
the transistor’s collector is taken and used to drive another circuit as
shown in Fig. 6, a minute dark current flows to the relay even if the
transistor is off. This may cause the problems described above.

Fig.
6 Connection to the next stage through collector
RELAY DRIVE BY MEANS OF SCR
.Ordinary
drive method
For SCR
drive, it is necessary to take particular care with regard to gate
sensitivity and erroneous operation due to noise. (Fig. 7)

Fig.7
.Caution
points regarding ON/OFF control circuit
(When
used for temperature or similar control circuits)
When the
relay contacts close simultaneously with an AC single phase power
source, because the electrical life of the contacts suffers extreme
shortening, care is necessary. (Fig. 8)

Fig. 8
1. When the relay is turned ON and OFF using a SRC, the SRC serves as a half wave power source as it is, and there are ample cases where the SRC is easily restored.
2. In this manner the relay operation and restoration timing are easily synchronized with the power source frequency, and the timing of the load switching also is easily synchronized.
3. When the load for the temperature control is a high
current load such as a heater, the switching can occur only peak values
and it can occur only at zero phase values as a phenomenon of this type
of control. (Depending upon the sensitivity and response speed of the
relay)
4.
Accordingly, either an extremely long life or a extremely short life
results with wide variation, and it is necessary to take care with the
initial device quality check.
RELAY DRIVE FROM EXTERNAL CONTACTS
Relays for PC board use have high sensitivity and high speed response characteristics, and because they respond sufficiently to chattering and bouncing, it is necessary to take care in their drive.
When the frequency of use is low, with the relay in response time caused by a condenser, it is possible to absorb the chattering and bouncing. (Fig. 9) (However, it is not possible to use only a condenser. A resistor should also be used with the capacitor.)

Fig. 9
ELECTRNIC CIRCUIT DRIVE BY MEANS OF A RELAY
.Chatterless
electronic circuit
Even
though a chatterless characteristic is a feature of relays, this is to
the fullest extent a chatterless electrical circuit, much the same as a
mercury relay. To meet the requirement for such circuits as the input to
a binary counter, there is an electronic chatterless method in which
chattering is absolutely not permissible. Even if chattering develops on
one side, either the N.O. side contacts or the N.C. side contacts, the
flip flop does not reverse, and the counter circuit can be fed pulsed
without a miss. (However, bouncing from the N.O. side to the N.C. side
must be absolutely avoided.) (Fig. 10)

Fig. 10
.Triac
drive
With an
electronic circuit using a direct drive from a triac, the electronic
circuit will not be isolated from the power circuit, and because of
this, troubles due to erroneous operation and damage can develop easily.
The introduction of a relay drive is most economical and most effective
solution. (Photo coupler and pulse transformer circuit are complicated.)
When a
zero cross switching characteristic is necessary, a solid state relay (SSR)
should be used. (Fig. 11)

Fig. 11
PC
BOARD DESIGN CONSIDERATION
.Pattern
Layout for Relays
Since
relays affect electronic circuits by generating noise, the following
point should be noted.
Keep
relay away from semiconductor devices. Design the pattern trances for
shortest lengths. Place the surge arrester (diode, etc.) near the relay
coil. Avoid routing pattern trances susceptible to noise (such as for
audio signals) underneath the relay coil section. Avoid though-holes in
places which cannot be seen from the top (e.g. at the base of the
relay). Solder flowing up through such a hole may cause damage such as a
broken seal. Even for the same circuit, pattern design considerations
which minimize the influence of the ON/OFF operations of the relay coil
and lamp on other electronic circuits are necessary. (Fig. 12)

Fig.
12
.When
it is necessary to use hand soldering for one part of a component after
dip soldering has been done
By providing a narrow slot in the circular part to the foil pattern, the
slot will prevent the hole from being plugged with solder. (Fig. 13)

Fig.
13
.When
the printed circuit board itself is used as a connector
The edge
should be beveled. (This prevents peeling of the foil when the board is
inserted into its socket.)
When
only a single side is used as the connector blade, if there is a
distortion in the circuit board, contact will be defective. Care should
be taken. (Fig. 14)

Fig.
14
A Relay
TTi Soldering and Cleaning Guide
|
Process |
Guideline |
|
1. Mounting of relay
|
.Avoid
bending the terminals to make the relay self-clinching.
.Relay
performance cannot be guaranteed if the terminal are bend. |
 |
|
2. Flux coating
 |
.Adjust
the position of the PC board so that flux does not overflow onto
the top of it.
.Use
rosin-based flux, which is non-corrosive and required no
washing.
.Do
not use Automatic Flux coating Method to dust-cover type relays.
.Do
not overflow onto the top of PC Board, in which a case, the flux
may even penetrate a flux-esistant type relay. |
3. Preheating
 |
.Preheating
acts to improve solderability.
.Preheating
according to the following conditions.
|
Temperature |
100°C
212°F
or less |
|
Time |
Without approx. |
|
4. Soldering

|
|
Automatic Soldering |
Hand Soldering |
|
.Flow
solder is the optimum method for soldering.
.Adjust
the level of the solder so that it does not overflow
onto the top of the PC board.
.Unless
otherwise specified, solder under the following
conditions depending on the type of relay. |
?Keep
the tip of the soldering iron clean. |
|
Soldering iron |
30W to 60W |
|
Iron Tip Temperature |
Approx. 300°C
572°F |
|
Soldering Time |
Within approx. 3 seconds |
|
Solder |
H60 or H63 |
|
Solder Temperature |
Approx. 250°C
482°F |
|
|
Soldering Time |
Within approx. 5 second |
|
Solder |
H60 or H63 |
|
5. Cooling
 |
|
Automatic Soldering |
Hand Soldering |
|
.Immediate
air cooling is recommended to prevent deterioration of
the relay and surrounding parts due of soldering heat.
.Although
the environmentally sealed type relay (plastic sealed
type, etc.) can be cleaned, avoid immersing the relay
into cold liquid (such as cleaning solvent) immediately
after soldering. Doing so many deteriorate the sealing
performance. |
|
|
6. Cleaning

|
.Do
not clean dust-cover type relays and flux-resistanct type relays
by immersion. Even if only the bottom surface of the PC board is
cleaning (e.q. with a brush), careless cleaning may cause
cleaning solvent to penetrate the relay.
.Plastic
sealed type relays can be cleaning by immersion. Use a Freon-or
alcohol-based cleaning solvent. Use of other cleaning solvent.
(e.g. Trichlene, chloroethene, thinner, benzyl alcohol) may
damage the relay case. However, some type of relays use
materials which are chemical resistant. Select the suitable
relay or solvent compatibility chart below.
.Cleaning
with the boiling method is recommended. Avoid ultrasonic
cleaning on relays. Use of ultrasonic cleaning may cause breaks
in the coil or slight sticking of the contacts due to the
ultrasonic energy. |
7. coating

|
.Do
not coat dust-cover type relays and flux-resistant type relays,
since the coating material may penetrate the relay and cause
contact failure.
.Do
not use this coating method in TTi
relay. |

Fig.
11 Automatic soldering process
|